Description
- For general information concerning the operation of a Hydrobloc control valve, please consult our general manual ( series K ).
- Extensive range including two different designs:
– XG design:
– Large flow capacity
– Low head loss
– Watertight at zero flow rate.
– XGS design:
– Particularly suitable for pressure reduction
– Better cavitation resistance
– Watertight at zero flow rate.
Construction
- Self-lubricated double guided mobile unit.
- Ductile iron body and bonnet
- Stainless steel seat for standard version until DN 400 XG design and DN 600 XGS design.
- Powder epoxy coating
- Stainless steel bolting
- Stainless steel pilot circuit tube and fittings.
- Pilot circuit strainer with screen in stainless steel.
- Individually packed
Easy Operation and Maintenance
- Visual position indicator with manual drain
- Including isolating valve (s) for pressure gauges.
- Equipped with opening speed controller “RO” ( DN 50 to 300 XG design, and DN150 to 400 XGS design only ).
- Chamber isolating valve independent from the adjustment of the speed controller.
- Maintenance without disassembly from the pipeline
- Easy dismantling from the top
- Drain plug ( stainless steel
Product according to standard EN 1074-S.
Technical data
- Range for XG design and XGS design
- PN 25
- Maximum temperature +10C to 650C
- Seating: class A according to standard ISO 5208 -2
- Face to face dimensions according to standards EN 558-1 series 1 ( except DN1000 ) and ISO 5752 series 1 ( except DN1000 ).
- Flange drilling according to standards EN 1092-2 and ISO 7005-2: ISO PN 10, 16 or 25 for DN 50 to 1000 ( other drillings, please consult us ).
- Fluid: drinking water or 2 mm filtered untreated water.
- Working Pressure 25 Bar.
- Vertical & Horizontal intallation
- The valve body of PN 16 and PN25 are the same, the difference are on flange drilling and pilot circuit
Specifications
- XGS design:
– B– : 835 mm
– C– : 847 mm
– D– : 422.5 mm
– Weight : 717 kg - XG design:
– B– : 1085 mm
– C– : 1229 mm
– D– : 422.5 mm
–Weight : 1205.0 kg