FIRE PUMP STANDART SDS Design Features According to UL & FM :
- All interior bolt or screw that are exposed to pumped liquid shall be of rolled bronze or corrosion resistant material
- The pump shall be provided with automatic air release valve, circulation relief valve and pressure gauges
- Bearings shall have an L-10 rating of not less than 5000 hours at maximum load.
- The pumps shall be provided with at least four packing rings plus a lantern ring. The lantern ring may be permitted to replace one ring of packing
- Impellers, wear rings, shafts, lantern rings, glands shall be made of corrosion resistant material
- Following material specifications are applied to STANDAT UL/FM fire pumps
Descriptions Of STANDART PUMP SDS FIRE PUMP :
- Horizontal single stage, double suction centrifugal pumps with closed impeller.
- UL Listed and FM Approved.
Specifications
- Discharge Flange : DN 65…..150 mm
- Capacity : 100…..2500 GPM
- Head : 85 to 208 PSI
- Speed : up to 3000 rpm
- Casing Pressure : 16 bar
Material
- Casing : Ductile Cast Iron
- Impeller : Bronze
- Shaft : Stainless Steel
Shaft Sealing
- Soft packing seal
Certification
- UL Listed, FM Approved, EN ISO 9905, CE, GOST-R