Allows you to measure insulation resistance more safely by avoiding operation mistakes
- Hot-line state ( 30V minimum ) detection
- Large volt mark with the buzzer sound
- Automatic data hold function
- Bargraph just like analog meter
- Large display with backlight
- Easy to use & tough body
Display : Numeral display 4000
Sampling rate : 2 times/sec.
Safety : IEC61010 CAT.III 600V
Optional accessories
Clip adapter : CL-16
Test lead : TLF-120 ( MG500 Only )
MG100 | Measuring range | Best Accuracy | Resolution |
MΩ | 4M/40M/400M/4000M | ± ( 3% + 4 ) | 0.001MΩ |
Test voltage | 500/250/125V | ||
ACV/DCV | 600V ( AC/DC Automatic detection ) | ± ( 3% + 2 ) | 1V |
Ω | 4000 Ω ( Buzzer and ALARM indicator ) | ± ( 3% + 3 ) | 1Ω |
Ω | 40Ω | ± ( 3% + 10 ) | 0.01Ω |
Open circuit voltage | 1 to 1.3 times of nominal test voltage | ||
Rated current | 1.0 – 1.2mA | ||
Short-circuit current | 2mA or less | ||
Live circuit detection | At ≥ 30V AC/DC or more, inhibits test, buzzer sound and ALARM indicator lights up | ||
Battery | R6X6 | ||
Size / Mass | H170XW142XD57mm/approx. 600g | ||
Standard accessories included | Test lead ( TL-112a), Strap ( ST-50), Instruction Manual |