GRUNDFOS MPC E4 CR10-3 Booster systems Pump with frequency converter control. Pressure booster system supplied as compact assembly according to DIN standard 1988/T5. The pumps are CR pumps connected to an external Grundfos CUE frequency converter.
- Hydro MPC-E maintains a constant pressure through continuous adjustment of the speed of the pumps.
- The system performance is adapted to the demand through cutting in/out the required number of pumps and through parallel control of the pumps in operation.
- Pump changeover is automatic and depends on load, time and fault.
APPLICATIONS GRUNDFOS MPC E4 CR10-3 :
Grundfos Booster Pump Suitable for :
- Water Treatment Fertigation, Chemigation & Dosing
- Controls & Digital Groundwater Management
- Drip, Micro Spray & Soaker Hose Irrigation
- Frost protection
- Rotor & spray irrigation
- Livestock & Wildlife Watering
- Livestock watering with solar solutions
- Pivot & Lateral Irrigation
- Agriculture solar solutions
- Solar boosting and water supply solutions
- Ground water transfer
- Commercial heating and water pressure boosting
- District cooling and heating
- Drinking water treatment
- Irrigation
- Industrial cooling
- Desalination
- Industrial heating, cleaning process, water supply & transfer
- Solar Controls & Digital Water Management
- Solar Water Treatment Fertigation & Dosing
- Community water supply, solar solutions
- Municipal solar solutions
- Water distribution
- Wastewater treatment
PUMP OPERATION
Dry-running protection and diaphragm tank are available according to the list of accessories. Pump operation is controlled by Control MPC with the following functions:
- Intelligent multi-pump controller, CU 352.
- Constant pressure control through continuously variable adjustment of the speed of each individual pump.
- PID controller with adjustable PI parameters (Kp + Ti).
- Constant pressure at setpoint, independent of inlet pressure.
- On/off operation at low flow.
- Automatic cascade control of pumps for optimum efficiency.
- Selection of min. time between start/stop, automatic pump changeover and pump priority.
- Automatic pump test function to prevent idle pumps from seizing up.
- Possibility of standby pump allocation.
- Possibility of backup sensor (redundant primary sensor).
- Manual operation.
- Possibility of external setpoint influence
- Log function
- Setpoint Ramp
- Possibility of digital remote-control functions:
- System on/off,
- Max., min. or user-defined duty
- Up to 6 alternative setpoints.
- Digital inputs and outputs can be configured individually.
- Pump and system monitoring functions:
- Minimum and maximum limits of current value
- Inlet pressure
- Motor protection.
- Sensors and cables monitored against malfunction.
- Alarm log with the previous 24 warnings/alarms.
- Display and indication functions:
- Colour Screen display
- Green indicator light for operating indications and red indicator light for fault indications
- potential-free changeover contacts for operation and fault.
- Grundfos bus communication
TECHNICAL DATA :
- Controls:
Dry running protection, mechanical: NONE - Liquid:
Pumped liquid: Water
Liquid temperature range: 5 .. 60 °C
Selected liquid temperature: 20 °C
Density: 998.2 kg/m³ - Technical:
Rated flow: 40 m³/h
Rated head: 23 m - Installation:
Range of ambient temperature: 5 .. 45 °C
Maximum operating pressure: 16 bar
Maximum permissible inlet pressure: 8 bar
Manifold inlet: DN80
Manifold outlet: DN80
Pressure rating: PN 16
Earth connection: PE
System design: G - Electrical data:
Power (P2) main pump: 1.1 kW
Mains frequency: 50 Hz
Rated voltage: 3 x 380-415 V
Rated current of system: 2.5 A
Start. method: Direct-on-line (DOL)
Enclosure class (IEC 34-5): IP54
Number of phases of main pump: 3