Valve Tozen GDRV101 1 Inch


Valve Tozen GDRV101 1 Inch are installed and used in centralised heating and cooling systems to obtain design flow rates of each terminal units and balancing the circuits in the building.

Valve Tozen GDRV101 1 Inch

Function

  • Balancing
  • Measuring
  • Pre-setting
  • Isolating

Features

  • Y-pattern globe design
  • Integral fixed orifice plate to form a fixed orifice flow measurement unit with regulation and isolation function.
  • Accuracy +/-5% at full open position of the valve
  • Equipped with 2 measuring nipples for differential pressure measurement
  • Microset handwheel adjustment with easily readable settings
  • Multi turn adjustment range for maximum flow control
  • Double regulating feature allows valve opening to be set with allen key
  • Long neck for thermal insulation
  • Bronze body of PN25 pressure rating
  • Comply to BS 7350

Specification

  • Type : Fixed orifice
  • Size Range : 15mm -50mm
  • Max. working pressure : 25 bar
  • Testing pressure : 37.5 bar (Shell)
    27.5 bar (Seat)
  • Working temperature : -100C to 1200C
  • Connection BS 21 (ISO7)
    ANSI B1 20.1
  • Standard : Comply to BS 7350

Materials

PartMaterialASTMEN
BodyBronzeB62 B83600EN1982 CC491K
BonnetDZR BrassB453 C35330EN12165 CW602N
StemDZR BrassB453 C35330EN12165 CW602N
DiscDZR BrassB453 C35330EN12165 CW602N
Onfice InsertDZR BrassB453 C35330EN12165 CW602N
Measuring NipplesDZR BrassB453 C35330EN12165 CW602N
O-ringEPDM
HandwheelABS

Dimensions

  • Size : 1 Inch ( 25 mm )
  • LxH : 105mm x 125mm
  • Weight : 0.8 kg
  • Kvs : 9.1